FSL020Z012054AA

FSL020Z012054AA

In Stock: 0

Please ask us for delivery time.

 

pdf-Logo   Manual

Dimensions w x h x l:0 x 0 x 0 mm
Weight net:111.0 kg
Construction type:C
Kind of defrosting:elektrisch
Voltage:400 V
Frequency:50 Hz
Expansion:Expansionsventil
Compressor:1.47 kW
Input:1658 W
Air throw:7.5 m
current consumption:4.3 A
Pressure line:10
Suction line:16
Evaporator diameter:254 mm
Evaporator fan number:3
Evaporator air volume:2364 m³/h
Condenser fan number:1
Condenser air volume:2120 m³/h
Condenser fan diameter:350 mm
Refrigeration output 32 °C stemp./100 mm/-15 °C:2267 W
Refrigeration output 32 °C stemp./100 mm/-20 °C:1862 W
Refrigeration output 32 °C stemp./100 mm/-25 °C:1479 W
Refrigeration output vol 32 °C stemp./100 mm/-15 °C:27.9 m³
Refrigeration output vol 32 °C stemp./100 mm/-20 °C:16.7 m³
Refrigeration output vol 32 °C stemp./100 mm/-25 °C:9.3 m³
Refrigeration output 43 °C stemp./100 mm/-15 °C:1786 W
Refrigeration output 43 °C stemp./100 mm/-20 °C:1454 W
Refrigeration output 43 °C stemp./100 mm/-25 °C:1137 W
Refrigeration output vol 43 °C stemp./100 mm/-15 °C:20.4 m³
Refrigeration output vol 43 °C stemp./100 mm/-20 °C:11.2 m³
Refrigeration output vol 43 °C stemp./100 mm/-25 °C:6.7 m³
  • Refrigeration unit in split variant. Available with screw or solder terminals.
  • General features
  • Condensing water direct discharge incl. heating
  • Remote control panel with 10 m long cable
  • Electronic control panel with temperature display
  • High pressure switch
  • Power lead 2.5 m with plug. Protection on site
  • Door switch with 10 m long cable
  • Cold room light with 10 m long cable
  • Refrigerant charge for devices with screw terminals
  • Nitrogen gas for devices with solder terminals
  • Connection cable 10 m for door heater
  • Calculation Conditions
  • Product entering temperature: -7 °C
  • Load density: 250 kg/m³
  • Product daily turnover: 10 %
  • Product cooling time per day: 18 h
  • Product specific heat (meat): 3,22 J/kg °C
  • Cold room isolation: 100 mm
  • Optional items
  • Water condensation
  • Pre-charged connection pipe 2,5 m
  • Different voltage
  • Data gathering and remote control
  • Condenser 4 A fan speed variator
  • Crankcase heater
  • Low pressure switch
  • Voltage monitor
  • Differential thermomagnetic switch
  • Master/Slave Function
  • Connection piece for refrigerant lines
  • Pre-charged connection pipe 5m
  • Pre-charged connection pipe 10m
  • Pre-charged connection pipe 15m
  • Required for outdoor installation:
  • Winter regulation when using <+5 ° C ambient temperature: Consists of speed control for condenser fan 4 A and crankcase heater. A low pressure switch is also recommended. Be covered when mounted outside the unit must always.